Overview
SM I/O Option Modules
Our I/O option modules and remote I/O units extend the drives
standard analogue and digital I/O to allow our onboard drive
automation and motion controllers to be at the heart of your
system.
SM-I/O 32
Extended digital I/O adding 32 bi-directional I/O points
| Unidrive SP |
Commander SK |
Digitax ST |
Mentor MP |
|
√
|
√
|
√
|
√
|
- 32 x Digital high-speed, bi-directional I/O
SM-I/O Plus
Extended I/O interface to increase the number of I/O points on a
drive
| Unidrive SP |
Commander SK |
Digitax ST |
Mentor MP |
|
√
|
X
|
√
|
√
|
- 2 x Analog Inputs (10-bit plus sign, +/- 10V)
- 1 x Analog Output (10-bit plus sign, +/- 10V)
- 3 x Digital Inputs/Outputs
- 3 x Digital Inputs
- 2 x Relay Contacts (2A @ 240V, 4A @ 30VDC)
SM-I/O Lite
Extended I/O inteface with reduced functionality
| Unidrive SP |
Commander SK |
Digitax ST |
Mentor MP |
|
√
|
√
|
√
|
√
|
- 1 x Analog Input(+/- 10V bi-polar or 4-20mA)
- 1 x Analog Output (0-10V or 4-20mA)
- 3 x Digital Output
- 1 x Relay Contacts (2A @ 240V, 4A @ 30VDC)
- Quadrature Reference Encoder Input
SM-I/O Timer
Extended I/O option module with real time clock
| Unidrive SP |
Commander SK |
Digitax ST |
Mentor MP |
|
√
|
√
|
√
|
√
|
- Access to Year, Month, Day, Hour, Minute, Second, and Daylight
Savings Mode.
- 1 x Analog Input(+/- 10V bi-polar or 4-20mA)
- 1 x Analog Output (0-10V or 4-20mA)
- 3 x Digital Output
- 1 x Relay Contacts (2A @ 240V, 4A @ 30VDC)
- Quadrature Reference Encoder Input
SM-I/O PELV
Namur standard I/O interface with high speed I/O
| Unidrive SP |
Commander SK |
Digitax ST |
Mentor MP |
|
√
|
√
|
√
|
√
|
This module provides PELV (Protective Extra Low Voltage) double
insulated digital and Analog I/O to meet IEC61131-2, Clause 3.3.1
Type as well as NAMUR NE37 specifications for chemical industry
applications.
- 1 Analog Input (current/voltage mode)
- 2 Analog Outputs (0-20mA, 20-0mA, 4-20mA and
20-4mA)
- 1 Digital Input
- 4 Digital Inputs/Outputs
- 2 Relay Contacts (2A @240VAC, 4A @ 30VDC)
SM-I/O 120
This module provides digital I/O rated to 120VAC
| Unidrive SP |
Commander SK |
Digitax ST |
|
√
|
√
|
√
|
- Conforms to IE6 1131-2 120 VAC Standard
- 6 Digital Inputs (120VAC or 3 Digital Inputs @ 240VAC)
- 2 Relay Contacts (2A @ 240VAC, 4A @ 30VDC)
SM-I/O 24V Protected
Designed as an over voltage protected I/O Solution
Module
| Unidrive SP |
Commander SK |
Digitax ST |
Mentor MP |
|
√
|
√
|
√
|
√
|
- 2 x Analogue Outputs (0-20mA, 20-0mA, 4-20mA and
20-4mA)
- 4 x Digital Inputs/Outputs
- 3 x Digital Inputs
- 2 x Relay Contacts (30VDC)
CTNet I/O
Flexible I/O system for remote connectivity using Control
Techniques' CTNet drive-to-drive network

| Unidrive SP |
Commander SK |
Digitax ST |
Mentor MP |
|
√
|
X
|
√
|
√
|
Pumping Application Interface - Soft Starter Extended
I/O
The Pump Application Interface expands the soft starter's input
and output functionality and is ideal for applications where
greater control and feedback are required.

| CSX |
CSXi |
IMS2 |
EMX3 |
|
√
|
√
|
X
|
X
|
Inputs
- Low pressure (allows pump priming and detection of broken
pipes)
- High pressure (protects against blocked pipes)
- Low water level (protects against dry pumping)
- PT100 (monitors pump temperature)
Configuration
- Low pressure enable delay
- Selectable trip delays
- Selectable temperature trip point
click here to view
catalog pages with more information about our I/O options
including terminal pin out diagrams.